Circuit breaker size calculator

Enter power or current to find the circuit breaker to fit, which curve suits, and whether your chosen cable can carry it. Works for single- and three-phase.

Indicative The result checks overload protection. Confirm the choice against your national wiring rules (IEC 60364, BS 7671). It does not check short-circuit tripping, RCDs or starting current.

How the breaker is chosen

Ib = P / (U · cos φ)            single-phase
Ib = P / (√3 · U · cos φ)       three-phase
In = smallest standard rating ≥ Ib
Ib ≤ In ≤ Iz                    overload protection condition

Worked example

A 7 kW single-phase hob fed by 2.5 mm² PVC copper cable in conduit (method B1) at 30 °C:

Ib = 7000 / 230 = 30.43 A
In = 32 A
Iz (2.5 mm², B1) = 24 A  <  32 A   ✘
Minimum cross-section for 32 A: 4 mm²

A 32 A breaker does not suit 2.5 mm². 4 mm² carries exactly 32 A, so in practice you often go one size up, especially on long runs where voltage drop also matters.

Maximum power for each breaker

At cos φ = 1. For loads with a lower power factor (motors), the permitted active power is proportional to cos φ.

Breaker (A)Single-phase 230 V (kW)Three-phase 400 V (kW)
61.384.16
102.36.93
163.6811.09
204.613.86
255.7517.32
327.3622.17
409.227.71
5011.534.64
6314.4943.65
8018.455.43
1002369.28
12528.7586.6

Tripping curves

CurveMagnetic tripTypical loads
B3–5 × InLighting, sockets, resistive loads
C5–10 × InSmall motors, air conditioners
D10–20 × InTransformers, heavy-start motors

Trip ranges per IEC 60898-1. The curve the calculator suggests is indicative.

Frequently asked questions

What size circuit breaker do I need for a given power?

Work out the current I = P / (U · cos φ) (three-phase: I = P / (√3 · U · cos φ)) and pick the smallest standard breaker at or above it. For example, 3.5 kW at 230 V is 15.2 A, so a 16 A breaker. The breaker must also suit the cable: you cannot fit 32 A on a cable that carries 24 A.

Why can the breaker not be larger than the cable can carry?

The breaker has to protect the cable. The condition is Ib ≤ In ≤ Iz: load current, at most the breaker rating, at most the cable’s current-carrying capacity. If the breaker exceeds Iz, the cable can overheat dangerously without the breaker tripping.

What is the difference between B, C and D curves?

The magnetic trip threshold differs: curve B trips at 3–5 × In, curve C at 5–10 × In, curve D at 10–20 × In. B suits lighting and sockets, C small motors and air conditioners, D transformers and heavy starting loads. The final choice also depends on circuit length and supply impedance.

Does the calculator check short-circuit tripping?

No. It checks overload protection only (Ib ≤ In ≤ Iz). Short-circuit tripping depends on the fault loop impedance and circuit length and must be verified separately. RCD protection is not covered either.

Does it work for motors?

It sizes the breaker for the rated current and suggests curve C. Starting current (5–8 times rated) is not included, and larger motors are usually protected with a thermal overload relay and contactor.

What about loads above 125 A?

Above 125 A you no longer use a modular MCB but a moulded-case circuit breaker (MCCB) or a breaker with adjustable trip units, sized by a designer.