Voltage drop calculator

Work out the voltage drop on a cable, the smallest cross-section that meets your limit, and the longest run you can use. Single- or three-phase, copper or aluminium.

How voltage drop is calculated

The calculator uses the IEC 60364-5-52 method, which includes cable reactance:

ΔU = b · I · L · (ρ / S · cos φ + λ · sin φ)
ΔU% = ΔU / U · 100

Worked example

A 16 A socket circuit, 30 m from the board, 2.5 mm² copper, resistive load (cos φ = 1):

ΔU = 2 · 16 · 30 · 0.0225 / 2.5 = 8.64 V
ΔU% = 8.64 / 230 · 100 = 3.76%

That passes the 5% limit for sockets but would fail 3% for lighting. With 4 mm² the drop falls to 2.35%.

Typical voltage drop limits

SupplyLightingOther uses
Public low-voltage network3%5%
Private LV supply (own transformer)6%8%

Values from IEC 60364-5-52, Annex G. Your national wiring rules may set different limits.

Maximum run lengths (single-phase 230 V, copper, cos φ = 1)

CurrentSectionMax at 3%Max at 5%
10 A1.5 mm²23 m38 m
16 A2.5 mm²23 m39 m
20 A4 mm²30 m51 m
25 A6 mm²36 m61 m
32 A6 mm²28 m47 m
32 A10 mm²47 m79 m
40 A10 mm²38 m63 m

Frequently asked questions

What voltage drop is allowed?

IEC 60364-5-52 recommends 3% for lighting and 5% for other uses when supplied from the public low-voltage network, measured from the origin of the installation to the load. National rules may differ, so check yours.

Do I enter the round-trip length?

No. Enter the one-way route length from the board to the load. The calculator multiplies by 2 for single-phase and by √3 for three-phase.

Is a cable that passes the voltage-drop check big enough?

Not necessarily. It must also carry the load current without overheating for its installation method, and be coordinated with the protective device.

Why does aluminium have a larger drop?

Aluminium has roughly 60% higher resistivity than copper, so at the same cross-section it loses more voltage. A size one or two steps larger is typical.