Heat pump size calculator
Enter floor area, insulation level and climate to see the heat pump capacity you need, the electrical input and which breaker to work out.
Indicative A simplified method based on specific heat loss per floor area. It does not replace a room-by-room heat loss calculation (EN 12831) by a designer. Compare the result with the datasheet capacity at the design temperature.
Monthly heat pump energy
Basic heat pump sizing remains available above.
Default temperatures are illustrative, not local weather. Replace them with verified monthly climate data for your location. The existing winter design zone does not supply annual weather.
Screening estimate, not EN 12831 or certified SCOP. Transmission = Σ(U × exposed area) × ΔT; ventilation = 0.335 × airflow × ΔT, recovery applies only to mechanical ventilation. Ground temperature is approximated by outdoor temperature; thermal bridges and solar/internal gains are not separately modeled. Monthly space heat uses a user-defined balance temperature. COP is an illustrative Carnot-fraction model unless manufacturer points are supplied (inverse-distance interpolation within the supplied temperature bounds; no extrapolation). Defrost/cycling losses use a fixed 10% allowance. Hot water always uses the illustrative COP model. Hot water uses 1.163 Wh/litre/K; no cylinder losses are included.
Import is local and applied only by this button. Monthly data stays monthly; hourly data stays hourly. Heat pump consumption is added to the existing household profile, so exclude it from the base demand to avoid double counting.
How it is calculated
q = q_ref · (Ti − Te) / 35 · (h / 2.6) specific heat loss, W/m² Q_heating = q · A / 1000 kW Q_hot water = people · 0.25 kW Q = (Q_heating + Q_hot water) · (1 + reserve) total need, kW P_el = Q / COP electrical input
- q_ref = specific loss at ΔT = 35 K (20 °C inside, −15 °C outside) and 2.6 m ceiling, by insulation level (table below)
- Ti, Te = indoor temperature and the zone’s outdoor design temperature
- Reserve covers defrost cycles and distribution losses (default 10%)
Worked example
A 120 m² well-insulated house in climate zone II (−15 °C), with 4 people for hot water and COP 2.8:
q = 55 · (20 + 15)/35 = 55 W/m² Q_heating = 55 · 120 / 1000 = 6.6 kW Q_hot water = 4 · 0.25 = 1 kW Reserve 10% = 0.76 kW Q = 8.36 kW → a 9 kW heat pump P_el = 8.36 / 2.8 = 2.99 kW → ≈ 13.7 A single-phase or 4.5 A three-phase
Specific heat loss by insulation level
| Level | q_ref (W/m²) | Description |
|---|---|---|
| Very good (estimate 35 W/m²) | 35 | New build, thick insulation, high-performance windows. Not a certified passive house: the Passive House standard targets about 10 W/m² |
| Good | 55 | Built to current standards (nZEB) or thermally upgraded |
| Average | 75 | Built after 1990, partly insulated |
| Poor | 110 | Old house, pre-1990, uninsulated |
Climate zones and outdoor design temperatures (Romania)
| Zone | Outdoor design temperature (°C) |
|---|---|
| I | -12 |
| II | -15 |
| III | -18 |
| IV | -21 |
| V | -24 |
Per SR 1907-1. A town’s zone is shown on the winter climate zoning map (in Romanian). Outside Romania, use your own outdoor design temperature.
Recommended size (kW) by floor area and insulation
Zone II (−15 °C), 4 people for hot water, 10% reserve, 2.6 m ceilings.
| Area | Very good | Good | Average | Poor |
|---|---|---|---|---|
| 80 m² | 5 kW | 6 kW | 8 kW | 11 kW |
| 100 m² | 5 kW | 8 kW | 10 kW | 14 kW |
| 120 m² | 6 kW | 9 kW | 11 kW | 16 kW |
| 150 m² | 7 kW | 11 kW | 14 kW | 20 kW |
| 200 m² | 9 kW | 14 kW | 18 kW | 26 kW |
Calculated with the same formulas as the calculator. Also check the circuit breaker and cable size for the unit’s supply.
Frequently asked questions
What size heat pump do I need for a 100 or 150 m² house?
It depends more on insulation than on floor area. As a guide, in a well-insulated house in climate zone II, 100 m² needs about 7 kW of heat (including hot water for 4 people), i.e. an 8 kW unit, and 150 m² about 10 kW, i.e. 11 kW. An old uninsulated house needs much more for the same area. The table on this page shows values by insulation level.
Why compare with the capacity at the design temperature, not the nominal one?
The nominal capacity in catalogues is usually measured at A7/W35 (air 7 °C, water 35 °C). In cold weather, when you need it, the heat pump’s output drops. So compare the need at the design temperature with the datasheet capacity at a close point, for example A−7/W35.
How do I choose the climate zone?
The zone follows the location, per the Romanian standard SR 1907-1 (winter climate zoning map). The outdoor design temperature runs from −12 °C in zone I to −24 °C in zone V. If you do not know the zone, look the town up on the map or enter the outdoor design temperature directly. For anywhere outside Romania use “Other outdoor temperature”.
Is a bigger heat pump better?
Not necessarily. A heavily oversized unit starts and stops often, which lowers efficiency, wears the compressor and costs more. The best choice is a size close to the real need, with a small reserve.
What breaker and cable does a heat pump need?
The calculator estimates the electrical input (the need divided by the COP) and the current. To size the breaker and cable use the unit’s datasheet (maximum current, including the backup electric heater if it has one) and the circuit breaker calculator.
Does it work for ground-source or air-to-air units?
The house’s heat demand is the same. What differs is the COP: ground-source units usually have a higher COP at low temperatures, so they draw less current. Enter the COP from your model’s datasheet.