Fault loop impedance and tripping calculator
Enter the breaker, cable and circuit length to see whether the breaker trips on a phase–PE fault and how long the circuit can be. For TN systems.
Indicative A calculated check does not replace measuring the loop impedance on the real installation. Confirm the result against your national wiring rules (IEC 60364, BS 7671). TN systems only.
How it is calculated
The method is a simplified conventional one, on the safe side: the voltage is reduced to 0.8 of U0, and conductor resistivity is raised 1.5 times above its 20 °C value to allow for heating during the fault.
r = 1.5 · ρ20 · (1/S_phase + 1/S_PE) Ω per metre x = 2 · 0.08 mΩ/m loop reactance Zs = Zs_board + √(r² + x²) · L Ik,min = 0.8 · U0 / Zs condition: Ik,min ≥ km · In km = 5 (B), 10 (C), 20 (D) L_max = (0.8·U0 / (km·In) − Zs_board) / √(r² + x²)
- ρ20 = 0.01724 Ω·mm²/m for copper, 0.02826 for aluminium; heating factor 1.5, voltage factor 0.8
- Zs_board = loop impedance at the start of the circuit (measured or estimated)
- km · In = upper edge of the breaker’s magnetic trip range (IEC 60898-1)
Worked example
C 16 A breaker, 2.5 mm² copper cable with a 2.5 mm² PE, 30 m, impedance at the board 0.4 Ω:
r = 1.5 · 0.01724 · (1/2.5 + 1/2.5) = 0.0207 Ω/m Cable Z = 0.0207 · 30 = 0.621 Ω Zs = 0.4 + 0.621 = 1.021 Ω Ik,min = 0.8 · 230 / 1.021 = 180 A Needed: 10 · 16 = 160 A → passes (margin × 1.13) L_max = 36.2 m
With the same breaker, a 50 m circuit on 2.5 mm² no longer passes. Fixes: 4 mm², curve B or a smaller breaker.
Maximum lengths (m), copper, PE equal to phase, board Zs 0.4 Ω
Curve B:
| mm² | 10 A | 16 A | 20 A | 25 A | 32 A |
|---|---|---|---|---|---|
| 1.5 | 95 | 55 | 41 | 31 | 21 |
| 2.5 | 158 | 91 | 69 | 51 | 36 |
| 4 | 253 | 146 | 111 | 82 | 58 |
| 6 | 380 | 220 | 167 | 124 | 86 |
| 10 | 633 | 367 | 278 | 207 | 144 |
| 16 | 1,013 | 587 | 444 | 331 | 231 |
Curve C:
| mm² | 10 A | 16 A | 20 A | 25 A | 32 A |
|---|---|---|---|---|---|
| 1.5 | 41 | 21 | 15 | 9 | 5 |
| 2.5 | 69 | 36 | 25 | 16 | 8 |
| 4 | 111 | 58 | 40 | 25 | 13 |
| 6 | 167 | 86 | 60 | 38 | 20 |
| 10 | 278 | 144 | 100 | 64 | 33 |
| 16 | 444 | 231 | 160 | 103 | 54 |
Values come from the same formulas as the calculator. A higher impedance at the board shortens the lengths. Also check the breaker choice and voltage drop.
Frequently asked questions
What is fault loop impedance and why does it matter?
It is the total impedance the fault current meets on its way phase → fault → protective conductor → source. The higher the loop impedance, the smaller the fault current. If it is too small, the breaker does not trip instantly and a fault can leave an exposed metal part live for longer than allowed.
Why is “instantaneous” tripping required?
In TN systems at 230 V, final circuits up to 32 A must disconnect within 0.4 s on a phase-to-earth fault (IEC 60364-4-41). If the fault current exceeds the breaker’s magnetic threshold (for curve C, between 5 and 10 × In) it trips in a fraction of a second. The calculator makes sure Ik,min exceeds the upper edge of that range, the safe threshold.
Why does curve B allow longer circuits than curve C?
Curve B trips magnetically at no more than 5 × In, curve C at no more than 10 × In. A lower threshold needs less fault current, so the loop can have a higher impedance, i.e. a longer cable. On long circuits with large breakers, switching from C to B is one of the fixes.
What value should I use for the impedance at the board?
Best is the value measured with a loop tester at the board. If you do not have it, 0.4 Ω is an indicative figure; on long or weak supplies it can be much higher. With a measured value the result is far more reliable.
If I have an RCD, do I still need this check?
An RCD adds protection against small fault currents, but this calculator only checks the MCB. If a circuit does not pass, whether an RCD can provide the disconnection is for the designer to decide under the wiring rules.
Does it work for TT systems?
No. It is for TN systems (TN-S and TN-C-S). In TT systems disconnection is verified through the earth electrode resistance with an RCD, which is a different calculation.