EV charger cable and breaker calculator
Pick the charger (3.7, 7.4, 11, 22 kW or your own value), the cable length and installation method, and see what cable and circuit breaker you need.
Indicative The result sizes the cable and breaker for the charger’s rated current. Confirm against your national wiring rules (IEC 60364-7-722, BS 7671) and the charger’s instructions. It does not check the RCD or the capacity of the supply.
How it is calculated
Ic = rated charger current (16 or 32 A on common models) In = smallest standard breaker ≥ Ic Iz ≥ In size by current capacity (IEC 60364-5-52 tables) ΔU% ≤ limit size by voltage drop
The recommended size is the larger of the two. More detail: cable size by current capacity, circuit breaker size and voltage drop.
Worked example
An 11 kW charger (three-phase, 16 A), 25 m from the board, multicore PVC copper cable in conduit (method B2), 30 °C:
Ic = 16 A → In = 16 A 1.5 mm²: Iz = 15 A < 16 A ✘ 2.5 mm²: Iz = 20 A ≥ 16 A ✔ ΔU = √3 · 16 · 25 · 0.0225 / 2.5 = 6.2 V = 1.56 % Cable: 5 × 2.5 mm²
Recommended size by charger and run length
Multicore copper cable, PVC, in conduit (method B2), 30 °C, one circuit, voltage drop up to 5%. For single insulated conductors in conduit (method B1) the current capacity is higher; pick the method in the calculator.
| Charger | Breaker | 10 m | 25 m | 50 m | 100 m |
|---|---|---|---|---|---|
| 3.7 kW, single-phase 16 A | 16 A | 3 × 1.5 | 3 × 2.5 | 3 × 4 | 3 × 10 |
| 7.4 kW, single-phase 32 A | 32 A | 3 × 6 | 3 × 6 | 3 × 10 | 3 × 16 |
| 11 kW, three-phase 16 A | 16 A | 5 × 2.5 | 5 × 2.5 | 5 × 2.5 | 5 × 4 |
| 22 kW, three-phase 32 A | 32 A | 5 × 6 | 5 × 6 | 5 × 6 | 5 × 10 |
Sizes are in mm², with the number of cores (3 single-phase, 5 three-phase). Calculated with the same formulas as the calculator; they change with other installation methods or high temperatures.
Frequently asked questions
What cable do I need for an 11 kW EV charger?
An 11 kW three-phase charger draws 16 A per phase. With multicore copper cable in conduit (method B2), 2.5 mm² carries 20 A and is usually enough, with voltage drop within limits for runs of a few tens of metres. The cable has 5 cores: three phases, neutral and earth. For long runs, hot locations or grouped cables the size goes up; the calculator takes that into account.
What circuit breaker should I fit for an EV charger?
The smallest standard rating that covers the charger current: 16 A for 3.7 kW single-phase and 11 kW three-phase, 32 A for 7.4 kW single-phase and 22 kW three-phase. The cable must satisfy Ib ≤ In ≤ Iz: the breaker cannot be larger than the cable can carry.
Should I add 125% because charging takes hours?
US rules (NEC) apply 125% to continuous loads. IEC standards used in Europe do not add such a factor, but charging runs for hours at full current, so the cable must carry the charger’s rated current permanently, i.e. Iz ≥ In. That is what the calculator does. In practice many people go one size up when the cable comes out exactly at its limit.
Which RCD does an EV charger need?
In general a dedicated type A RCD with 6 mA DC fault detection (many wallboxes have it built in) or a type B RCD. Exact requirements depend on the charger and your wiring rules, so follow the manufacturer’s instructions and check with a qualified electrician.
Single-phase or three-phase?
It depends on your supply. Single-phase tops out at 7.4 kW (32 A); three-phase gives 11 kW (16 A per phase) or 22 kW (32 A per phase). The calculator does not check the capacity of your supply; see your network operator’s connection terms.
Does it check short-circuit tripping?
No. Use the fault loop impedance calculator for that, especially if the charger is far from the board.