Heat recovery ventilation calculator
Enter floor area, occupants and wet rooms to see the air flow, the heat recovery unit you need, how much heat you recover and the main duct diameter.
Indicative Simplified sizing by the largest of three criteria. It does not replace a ventilation design (EN 16798) with room-by-room flows, pressure drops and noise levels.
How it is calculated
V_area = 1.512 · A m³/h (0.42 L/s per m², EN 16798-1 cat. II) V_occupants = 30 · n m³/h V_extract = 60·kitchens + 40·bathrooms + 20·WCs m³/h V = max(V_area, V_occupants, V_extract) ACH = V / (A · h) air changes per hour Unit ≥ V · (1 + reserve) Q_loss = 0.335 · V · ΔT W Q_with recovery = Q_loss · (1 − η) D = √(4 · V / (3600 · 3 · π)) main duct
Worked example
A 120 m² house, 2.6 m ceilings, 4 occupants, one kitchen, one bathroom and one WC, climate zone II (−15 °C), recovery unit efficiency 85%:
V_area = 1.512 · 120 = 181.4 m³/h V_occupants = 30 · 4 = 120 m³/h V_extract = 120 m³/h V = 181.4 m³/h (floor area) → 0.58 air changes per hour Unit ≥ 181.4 · 1.2 = 218 m³/h → 250 m³/h Loss: 0.335 · 181.4 · 35 = 2.13 kW → with recovery 0.32 kW Fans: 0.45 · 181.4 = 82 W Main duct: 146 mm → DN 160
Typical flows for common homes
One kitchen, 2.6 m ceilings, zone II, 85% efficiency, 20% reserve.
| Area | Occupants | Baths / WCs | Flow (m³/h) | Governed by | Unit (m³/h) |
|---|---|---|---|---|---|
| 60 m² | 2 | 1 / 0 | 100 | extract | 150 |
| 80 m² | 3 | 1 / 0 | 121 | floor area | 150 |
| 100 m² | 4 | 1 / 1 | 151 | floor area | 200 |
| 120 m² | 4 | 2 / 1 | 181 | floor area | 250 |
| 150 m² | 5 | 2 / 1 | 227 | floor area | 300 |
| 200 m² | 6 | 3 / 1 | 302 | floor area | 400 |
Calculated with the same formulas as the calculator. For the unit’s electrical supply use the circuit breaker calculator.
Frequently asked questions
How much fresh air does a home need?
Take the largest of three flows: by floor area (0.42 L/s per m² for new dwellings, category II of EN 16798-1, i.e. 1.51 m³/h per m²), by number of occupants (about 30 m³/h per person) and what is needed to extract air from bathrooms and the kitchen. For a 120 m² house with 4 people that is about 180 m³/h, roughly 0.6 air changes per hour. At 155 m² the area-based flow is 234 m³/h.
Why the largest of the three?
A balanced ventilation system supplies as much air as it extracts. In a small home with many people, occupants decide; in a home with many bathrooms, extract decides. The calculator shows which criterion governed.
What efficiency does a heat recovery unit have?
Good units claim 85% or more, and Passive House projects usually require at least 75%. The real figure in a home is generally lower than the catalogue value. Enter the datasheet value for your model.
How much does heat recovery cut ventilation heat loss?
At 85% efficiency the ventilation heat loss falls to 15% of its no-recovery value. In the worked example, from about 2.1 kW to about 0.32 kW at −15 °C. The loss is calculated at roughly 0.34 W for every m³/h and every degree of temperature difference.
How much electricity does a heat recovery ventilation system use?
The fans use little, tens of watts for an ordinary home (the calculator uses 0.45 W per m³/h). If the unit also has an electric preheater against frost, it may draw 1–2.5 kW and has to be allowed for in the supply. Check the datasheet and the circuit breaker calculator.
What duct diameter should I choose?
The calculator gives the main duct diameter at 3 m/s, a common upper limit for main runs in homes. Branches to rooms are sized for lower velocities (about 2 m/s) to avoid noise. Room-by-room distribution and pressure drop are for a designer.